 +====== Command:SAF ======
  
 +--> MS2000 or RM2000 syntax#
 +
 +^Shortcut ​ |SAF| 
 +^Format ​ |SAF [axis]=### …|
 +^Units ​   |milliseconds or clock edges|
 +^Remembered |Using SS Z |
 +
 +<--
 +
 +--> Tiger syntax# ​
 +
 +^Shortcut ​ |SAF| 
 +^Format ​ |SAF [axis]=### …|
 +^Units ​   |milliseconds or clock edges|
 +^Type    |Axis-Specific ​ |
 +^Remembered |Using [addr#]SS Z |
 +
 +<--
 +
 +This command sets the period of the pattern, in units of milliseconds in case of internal clock (default, see ''​SAP''​) or in number of clock edges for external clock. ​ Note that the triangle pattern and square wave pattern will automatically force themselves to have a period of an even number of milliseconds,​ even if the user specifies a period of an odd number of milliseconds. When period is set to be 1msec, the resulting behavior is undefined.
 +
 +**Note:** On MicroMirror the actual waveform output is modified by the filter (tunable with ''​BACKLASH''​),​ especially when the period is set to be less than 10msec.
 +
 +== Example ==
 +
 +<asi> $ SAF A=10  ​
 +:​A</​asi>​
 +Sets up the period of the pattern at 10msec or 100Hz.
 +
 +
 +
 +
 +